1. Application
This product is used in the fixed power transmission lines at mines.
2. Guide to Use
The max. conductor temperature in normal use is 90℃, and the max. conductor during short circuit (less than 5 seconds) is 250℃.
3. Code, Description and Usage
Code | Description | Usage |
MYJV | XLPE insulated PVC sheathed power cables for mining use | Used in power transmission lines of rated voltage 0.6/1kv and below at mines |
MYJV22 | XLPE insulated steel tape armored PVC sheathed power cables for mining use |
4. Specification
1) Structure
Code | Rated Voltage | No. of Cores | Sectional Area (mm2) |
MYJV | 0.6/1kV | 3 | 1.5-300 |
MYJV22 | 3 | 2.5-300 | |
MYJV | 3+1 | 4.0-300 | |
MYJV22 | 3+1 | 4.0-300 | |
MYJV | 4 | 4.0-185 | |
MYJV22 | 4 | 4.0-185 |
2) Insulation Thickness
Sectional Area (mm2) | Nominal Thickness (mm) | Sectional Area (mm2) | Nominal Thickness (mm) | Sectional Area (mm2) | Nominal Thickness (mm) |
1.5 | 0.7 | 25 | 0.9 | 150 | 1.4 |
2.5 | 0.7 | 35 | 0.9 | 185 | 1.6 |
4 | 0.7 | 50 | 1.0 | 240 | 1.7 |
6 | 0.7 | 70 | 1.1 | 300 | 1.8 |
10 | 0.7 | 95 | 1.1 | ||
16 | 0.7 | 120 | 1.2 |