CN

New energy cables

Cable in photovoltaic system

Cable in photovoltaic system

Cable implementation specification

he product is designed, manufactured and tested in accordance with the German 2 Pfg 1169/08.2007 technical specification.

TUV certification number and test report number

TUV certification No.: T50344566 01

TUV test report No.: 50042876 001

Product instruction

2 Pfg 1169/08.2007 is suitable for single-core flexible cables (wires) used on the CD side in photovoltaic systems with a maximum allowable 1.8KV (core to core, ungrounded system) DC voltage.

The product is suitable for use in Class II safety levels; cable operating ambient temperatures up to 90 ° C; cables can be used in parallel.

1.jpg

Characteristics

1.Rated voltage 

AC: U0/U 0.6/1KV

DC: 1.8KV (wire-conductor, ungrounded system, circuit under non-load conditions).

Maximum allowable working voltage:

AC:0.7/1.2KV AC: 0.7/1.2KV

DC:0.9/1.8KV DC: 0.9/1.8KV

2. Test voltage

AC:6.5KV/5min AC: 6.5KV/5min

DC:15KV/5min DC: 15KV/5min

3. Working temperature

Ambient temperature -40-120 ° C (mobile or fixed)

The maximum temperature during short circuit (within 5 s) does not exceed 200 °C.

4. The cable bend radius is not less than 4 times the cable diameter.

5. The cable insulation and sheathing materials are halogen-free flame retardant crosslinked polyolefin.

6. Cable thermal life 25 years

7. The finished cable has excellent weather resistance, UV and ozone resistance, and can withstand a wide range of temperature changes (from a deep cold -40 ° C to a high temperature 120 ° C mutation).

8. The cable has excellent penetration resistance and meets the technical specifications of TUV2Pfg 1169/08.2007.

2.jpg

Product specifications

Product type

cores

Nominal cross section(mm2)

PV1-V

1

1.5-16

Product structure

3.jpg

Schematic diagram of cable structure for photovoltaic system

Product structure size

Product specifications

Conductor structure

 

Conductor outer diameter (mm)

Insulation Thickness  (mm)

Sheath Thickness  

(mm)

Sheath outer    diameter  (mm)

Weight

(kg/km)

1*1.5

30/0.25

1.5

0.9

0.9

5.1

42

1*2.5

49/0.25

2.0

0.9

0.9

5.6

54

1*4

56/0.3

2.5

0.9

0.9

6.1

72

1*6

84/0.3

3.5

0.9

0.9

7.1

100

1*10

84/0.4

4.5

1.0

1.0

8.5

157

1*16

126/0.4

5.6

1.0

1.0

9.6

215

Cable reference current carrying capacity

Ambient temperature 60 ℃

Conductor temperature 120 ℃

Conductor nominal cross section(mm2)

Single core cable air laying (A)

Laying on the surface of the device (A)

Adjacent to the surface of the device (A)

1.5

2.5

4

6

10

16

30

41

55

70

98

132

29

39

52

67

93

125

24

33

44

57

79

107


Contact us

Add:No.268 jingwu road, economic development zone,
   yueqing city, zhejiang province
Service hotline:400-0700-118  Tel:0577-62667555